- Chemical and mechanical cleaning
- For one pH electrode PG 13.5
- Easy to install
- Installation at any time on the existing 9336 probe
When pH is measured, there is a risk of electrode fouling; result is a drift of measured value. To be free of this, it is necessary to clean carefully the electrode. The BAMO auto cleaning probe 9360 to designed to inject pressurized cleaning liquid on the electrode to remove impurities. (For instance: injection of hydrochloric acid to remove sodium carbonate.)
Note:
The probe 9360 can only be used with pH/ORP immersion probe 9336. The tubing for cleaner liquid is all inside the probe body. The auto-cleaning probe may be adapted at anytime on existing pH immersion probe 9336. The cleaner fluid, water or acid + water, is projected through 3 nozzles around the electrode, 2 mm close to the bulb. Fitting of the probe consist of an adjustable flange. The sliding DN 65 mm flange, allows adjustment of immersion depth.
The cleaning sequence can be set up through the BAMOPHAR or BAMOPHOX. During the cleaning, the regulation is switched on “STAND-BY”, not to interfere with the process..