CDP Metal Liquid Flow Switch

Brand: BAMO
BAMO Mesures CDP Metal Liquid Flow Switch, ISME Malaysia
  • 1 Reed contact N.O. / N.C.
  • Stainless steel or brass versions
  • Low pressure drop
  • Fittings: On tee up to DN50 or BSP ½”
  • Applications: Detection of presence or absence of flow of a liquid in a pipe under pressure. The liquid must be free of magnetic particles.
Body: AISI 316 Ti
Brass
Seal: FPM on stainless steel version
NBR on brass version
Temperature limit: 110 °C (other on request)
Ambient temperature: 70 °C
Pressure limit: 25 bar
Fittings: DN 10 to DN 50: Tee with BSP female threads
ND 50 and larger: male thread BSP ½”
Contact output: N.O. or N.C. according to the Reed contact orientation
Switching power: 230 V / 1.5 A / 80 W / 90 VA max.
Output cable: PVC; 3-wire; 1 mm² ; 1.5 m long
Trigger point adjustment: ±15 % of table values, horizontal pipe
(Refer to datasheet)
Protection: IP 65

 

Caution: Thresholds are for water at 20 °C and for a flow in horizontal pipe. Mounting could be on a vertical pipe with ascending flow; Then, threshold value will be greater than the one from the table. The pipe slope of a flowing down piping must be less than 40 %.

The BAMO CDP operates a switch outside the liquid: The flow drives the paddle. A magnet on top of paddle actuates a Reed contact, located outside the fluid. The reverse movement of the paddle is generated by a leaf-spring. These controllers offer a simple, reliable and inexpensive solution for flow monitoring in pipelines.

These controllers offer a simple, reliable and inexpensive solution for flow monitoring in pipelines.

CDP controllers are mounted in-line, pipes up to ND 50 with a Tee, BSPF threads. For larger diameters, CDP must be mounted on-line, on an adaptor BSP ½” female thread.

Note: The Reed contact has a low switching power: The use of a relay ES 2001 will protect the Reed and allows a remote loop signal with greater breaking capacity on a change-over relay output (500 VA/ 250 V A / 5A – 1A/ 125 V DC/ 40 W).