Skip to content

CDP 57 Liquid Flow Switch

Brand: BAMO
BAMO Mesures CDP 57 Liquid Flow Switch, ISME Malaysia
  • For clear liquids
  • Stainless steel or brass versions
  • For pipes from DN 50 up to DN 200
  • Mounting on-line, fitting with loose nut BSPF ½”
  • Applications: Detection of the presence or not of flow in a pipe under pressure. The liquid must be free of magnetic particles.
Materials:  Body and fitting in AISI 316 Ti with FPM seals
Body and fittings in brass with NBR seals
Fittings:   Male thread BSP ½”
Size: From DN 50 up to DN 200 mm
Temperature limits:  Liquid: -25 to 110 °C
Ambient: -25 to 80 °C
Pressure limit: PN 25
Contact: N.O. or N.C. (according terminals)
Operation: Flow below the switching point: Open contact
Flow over the switching point: Closed contact
Possibility to reverse the logic
Current limit:  Max. 1 A
Voltage limits:  Max. 230 V AC, 48 V DC
Switching power: Max. 26 VA, 20 W
Switching point:  ± 15 % of table values
Protection:  IP 65
Connector:  Plug DIN EN 175301-803-A

The flow of liquid drives the paddle which actuates a Reed contact via a magnet mounted on the top of the paddle. A second magnet in opposition, pushes back the paddle when flow is decreasing. This design allows the CDP 57 controller to be mounted in any position.

Mounting precautions: Mounting could be on a vertical pipe with ascending flow; Then, threshold value will be greater than the one of table. The pipe slope of a flowing down piping must be less than 40 %.

Note: An amplifier relay ES 2001 will protect the Reed contact and allows a switching power of up to 500 VA / 250 V AC / 5 A – 1 A / 125 V DC / 40 W).