- Local or remote display
- Analogue output(s) 4-20 mA
- Relay output(s)
- Interface RS485 with MODBUS RTU
- Applications:
- For automation of HVAC network
- Storage areas, cool stores, greenhouses, animal husbandry
- Museums, Data centers, weather stations
Model: | QM-212: Transmitter with integrated probe O.D. 18 mm, 90 mm high QM-612: Transmitter with cable output probe or with a M12 connector |
Power supply: | 24 V DC (11 to 36 V DC) – Consumption maxi 2.5 W |
Display: | Backlit, graphic LCD – 128 x 64 pixels |
Ambient temperature: | -20 to +70 °C (Version without display: -30 to +80 °C) |
Protection: | IP 65 (Version without display: IP 67) |
Housing: | Wall mounting Dimensions: 120 x 90 x 50 mm Materials: ASA ( Luran® ) and polycarbonate |
Probe for QM-212 model: | |
Type: | Integrated to the display unit |
Dimensions: | Height: 90 mm; O.D.: 18 mm |
Materials: | AISI 316 L; PTFE tap filter |
Temperature: | -30 to +105 °C (±0,2 °C from 10 to 60 °C) ±0.4 °C at 30 °C ; ±0.7 °C at 105 °C |
Humidity: | 0 to 100 % RH (±1.8 % RH from 20 to 80 % RH at 25 °C) |
Probes for QM-612 model: | |
Type: | Output cable, to connect to the housing |
Dimensions: | Length: 90 mm; O.D. 18 mm |
Materials: | AISI 316 L; PTFE tap filter Cable with PUR coating: Max. 80 °C; Or TPE: Max. 120 °C |
Temperature: | -40 to +120 °C (± 0.2 °C from 10 to 60 °C) ( ±0.4 °C at -30 °C ; ±0.7 °C at 120 °C ) |
Humidity: | 0 to 100 % RH ( ±1.8 % RH from 20 to 80 % RH at 25 °C ) |
Connections: | Cable gland or connector type M12 – 4 pins |
Outputs (options): | |
Relay outputs: | 0, 1 or 2 relay outputs, N.O. Rated: 24 V AC / 35 V DC, 200 mA |
Analogue outputs: | 0, 1 or 2 outputs: 0/4-20 mA (0/24 mA max.) Active signal, no galvanic insulation |
Interface: | RS485; 8N1 & 8N2; 1,200 to 115,200 bit/s; MODBUS RTU; no galvanic insulation |
BAMO Hygrowiz measures the temperature and relative humidity of the air. The temperature and humidity probe is integrated or cable connected to the housing. Standard version: the probe has a PTFE tap filter to limit the impact of water splashes (non-absorbent and anti-corrosion surface).
Choose the right version for your application, with remote signals, relay outputs, 4-20 mA signals, interface RS485 MODBUS protocol. Please, request more information when necessary.
HygroWiz is available as a blind version, without display. For an easy start-up, HydroWiz is set up before shipment, according to your request.