- Leak localization
- Length up to 3,000 metres (12 areas)
- Automatic recognition of loop parameters
- Event recording (date / time)
- Outputs: 4-20 mA, MODBUS RTU, relays
- Applications:
- Building automation
- Datacenters
- Semiconductor Industry
- Clean rooms
- Archives storage / Libraries / Museums
- Heating and air conditioning systems
- Switching centers, computers room
Power supply: | 100 to 240 V AC – 50/60Hz or 10 to 30 V DC; 12 to 24 V AC |
Consumption: | 2 to 5W |
Contact outputs: | 5 contacts, adjustable, potential-free To set as, or N.O. or N.C. contact Note: All contacts are open when de-energized |
Switching power: | 250 V AC, 2 A / 30 V DC, 1 A
Caution: Contacts are not protected against overload, provide an external protective device |
Maximum cable length: | 3,000 m |
Housing: | 46 x 100 x 127 mm Rail mounting (DIN EN 50 022; 35×7.5 mm) |
Protection: | IP40
Note: The protection against accidental contact according to DIN EN 61010-1 is only guaranteed when the unit is installed in a closed cabinet with a protection IP5x or greater. |
Ambient temperature limits: | -10 to +45 °C |
Sensor (cable) temperature limits: | -50 to +150 °C |
Connectors temperature limits: | -20 to +60 °C |
Wall-mount cabinet (option): | 175 x 200 x 155 mm |
Screw terminals: | Screw connectors, cable diam. Max. 1.5 mm² |
Detection areas: | 12 areas; Setting of name/ TAG to each one |
Accuracy of leak localization: | < 1 %; ±1 m |
Measuring loop: | 1 input for the 4 poles sensor (cable) 2 additional inputs for 2 one-point detectors (e.g. MAXITOP LWC or LWC B) |
Power supply to the detection loops: | Localization with sensor (cable): Max. 20 V AC/DC; Max. 5 mA One-point detectors: Max. 30 mA (each) |
Analogue output 4-20 mA | Active signal output (with its own loop power) 4 to 5 mA: No alarm 5 to 20 mA: Localization of the detected leak point = [ cable length x (current value – 5mA) ] / 15mA |
Adjustable timer: | When detection occurs: 0.5 to 5 minutes delay before signaling |
Real-time clock: | Integrated clock with battery, automatic summer time switch can be activated |
Records: | Automatic record of all events, max. 48 inputs, events can be acknowledged and deleted, individually |
Language: | To choose between English, German, French, Spanish, Portuguese, Polish |
Key protection of settings: | 4 digits; Can be deactivated |
Signaling interface: | Display: 2 line-text LCD Status of contact outputs 5 LED (multicolour) |
Digital communication: | RS485 / MODBUS |
Selecter: | Rotary switch on front panel |
Bamoleak allows securing work areas where leaks are prejudicial for equipment, by detecting and precisely locating leaks of conductive liquids. The sensor (cable) is laid along the monitored area or pipeline, and, connected to the evaluation unit. Leakage is detected by the converter, which determines, records and reports information via the analog output, relays and the RS485 Modbus interface.
Two complementary detectors can be connected to the converter such as Maxitop LW C (detection in double-walled tank) or LWC-B (local floor detector).
Note: BAMOLEAK can locate one leak at a time.