Skip to content

Maximat LW VK Leakage Detection Sensor

Brand: BAMO
BAMO Mesures Maximat LW VK Leakage Detection Sensor, ISME Malaysia
  • Float level fail-safe detection
  • For aggressive and non electrically conductive liquids
  • Positive active alarm
  • Auto diagnostic system and LED indication when in use with a SHR C transducer
  • Approvals: DIBT Z-65.40-272, for leakage detection, WHG §19 when in use with a SHR C transducer
Main power supply:  24 V DC ±10%; caution: DC current circuit should be protected by a fuse of 250 mA
Power consumption:  Approx. 3W
Operating pressure:  Atmospheric, 0.8 to 1.1 bar
Ambient temperature:  -20 to +60°C
Material:  PE-HD
Cable:  TPK, 2 x 0.5 mm2, shielded
Hysteresis:  About 2 mm
Terminal housing:  PBT, fibre glass reinforced, IP 65 acc. EN 60 529
Terminals:  Screw connectors, IP 20; max. wire cross-section 2.5 mm2
Output:   To a transducer MAXIMAT SHR C.
Cable length 300 m maximum,
wire cross section 0.5mm2 as a minimum

BAMO Maximat LW VK is ideal for permanently survey risks of leakage of a liquid from storage tanks, filling equipment, dosing pumps etc. Convenient to use with non-electrically conductive liquids, oils, emulsified, non-flammable, water endangering liquids. It is a perfect instrument to detect fluid in a double-wall tank. Maximat LW VK operates with liquids of specific weight from 0.7 g/cm3.

The sensor Maximat LW VK is designed to detect conductive liquids non-electrically conductive. The detection results from the position of a magnet inside the float and a Reed contact inside the probe. It is necessary to use it with a SHR C transducer. The liquids may not generate deposits originating jamming of float.