- All-plastic versions
- Integrated transmitter and connection for test button
- No moving parts
- Floor leak detection
- NPN / PNP interfaces
- Wet parts in plastic materials
Detection: | Capacitive high-frequency sensor, fail-safe detector |
Ambient temperature: | -20 to +60 °C |
Operating pressure: | Atmospheric; Limits: 0.8 to 1.1 bar |
Housing head: | PBT, fibre-glass reinforced |
Protection: | IP67 (not suitable for permanent immersion) |
Power supply: | 15 to 27 V DC |
Consumption: | < 1 W |
Cable: | PVC, 6 m long; 5x 0.34 mm² |
Outputs: | Potential-free Reed contact for low voltage (Normally closed, it opens when alarm occurs) – Rated: Max. 50 V AC / DC, Max. 0.5 A, Max. 10 VA, convenient for operating with a coupling relay or PLC, signaling device TC4 / TC1 or CST unit. 2-wire alarm output reporting with transmitter MAXIMAT SHR C Note: Simultaneous use of both outputs is not possible. |
Additional function: | Connection of an external test button (potential-free contact), for a complete diagnostic of the device integrity (connection loops, electronics). |
Connection options: | Alarm units: MAXIMAT TC1 / TC4 Coupling relay: CST Transmitter: MAXIMAT SHR C Automation with PLC |
BAMO Maximat LWC BX compact leak detectors are used to detect leakage or spread water-polluting liquids. Due to the short detection height of liquid, about 1mm, even a small leakage quantity is reliably detected. The device is used for leakage detection of water-polluting media.