Skip to content

Mempro S6.6 Hydrostatic Level Controller with 4 Switching Points

Brand: BAMO
BAMO Mesures Mempro S6.6 Hydrostatic Level Controller with 4 Switching Points, ISME Malaysia
  • 4 Adjustable relay outputs, N.O. or N.C.
  • The sensor is not in contact with liquid
  • Adjustable hysteresis and delay time for each channel
  • Automatic calibration for max. level
  • Integrated timer for the venting function
Power supply:   24 V DC (9 to 36 V)
Consumption:  Max. 1 W
Ambient temperature:  -20 to +60 °C (MEMPRO S6.6)
-15 to +60°C (MEMPRO C S6.6)
Liquid temperature:  PVC: 0 to +60 °C
PP: 0 to +90 °C
AISI 316: 0 to +90 °C
Output relays:  3 contacts +1 floating limit value contact
(3 switches + 1; the fourth relay also usable as a timer output -venting function- )
Switching power:  Rated: 250 V AC, 2A; 30 V DC, 1A

Note: The contacts are not protected against overload.

Head housing:  PBT, fibre-glass reinforced
Protection:  IP 65 according EN 60 529
Electrical connection:  Screw terminals, max. 1.5 mm²
Measuring cell:  Ceramic with EPDM sealing

Note: The controller may only be used with fluids for which its vapours are compatible with the EPDM seal of the sensor. When EPDM is only partially resistant to the chemical, care must be taken that the seal never comes into direct contact with the liquid during operation, assembly and maintenance.

Accuracy:  0.5% ± 0.5 Digit
Display in %:  Resolution of 1 %
Reset hysteresis:  Adjustable from 1 to 99 %
Signal filter:  Adjustable from 1 to 9.9 s
Signaling on PCB:  3 digits of 7 segments, LED display, 4 LEDs (relays)
Settings:  Combined rotary / push switch
Connection for venting function:  Through a hose (e.g. PVC 4x1mm) or by screwing a compressed air plug BSP 1/4” with tubing.

BAMO Mempro S6.6 is designed for universal level control for pressureless containers, aggressive fluids, storage container monitoring and batching operations. It works according to the hydrostatic pressure measuring principle. The output signal corresponds to the pressure of the atmosphere inside the measuring tube.

The ceramic sensor is not touched by the liquid. On-site, with the automatic calibration function, the instrument is paired to the tank size in a matter of minutes. Four trigger points can be assigned to level heights through the setting menu. All switching points have an adjustable delay time, an adjustable hysteresis and a switchable N.C./ N.O. function.

For a clogging or degassing liquid, or when the temperature fluctuates, the Mempro must be connected to a venting device (Mempro BL). The timer for venting function is integrated in the Mempro.