- Fit any water softener
- In-line monitoring
- Alarm set up at 10% of raw water hardness
- Automatic diagnostic of a complete system
- Applications: Control and monitoring of water quality between inlet and outlet of the softener
Water temperature: | < 30 °C |
Ambient temperature: | +5 to +50 °C |
Operating temperature: | -10 to +45°C |
% H.R.: | 30 to 80 % |
Power unit (included): | 100 to 240 V AC; 50/60 Hz; 0.2 A |
Power supplied: | 15 V DC; approx. 4 W |
Relay output: | N.C. contact; max. 24 V DC; 0.5 A; Alarm/ Fault on Threshold, Brine, Electrode, Solenoid valve |
Raw water inlet: | By-pass with fitting for PA tubing |
Inlet for softened water: | O.D..4 mm,; I.D. 2 mm, necessary filtration unit ( |
Pressure limits for raw water: | Min. 1 bar; Max. 10 bar (raw & softened waters) |
Drain outlet: | PA tubing; O.D. 8 mm; atmospheric pressure |
Raw water quality: | Drinkable water, free of grease, oil and brine, biol.: < 5000 KVE /ml |
Raw water hardness limits: | 2 to 100 °f (20 to 1000 ppm CaCO₃) |
Electrode check up: | Automatic test with an indication of low efficiency |
External cycling switch: | Pulse limit: >0.5 s |
Dimensions: | Wall mount cabinet: 120 x 80 x 55 mm (Overall: 250x220x100 mm) |
BAMO Bamosoft Smart monitors safely the water quality produced by the softener. It alarms (LED and relay output) when the softened water hardness is 10% or over the hardness of raw water.
Example :
- Raw water inlet = hardness of 300 ppm CaCO₃
- The system is alarming if softened water hardness > 30 ppm CaCO₃
Bamosoft Smart gives an alarm as well as brine (leakage) is detected at softener outlet and if system integrity is not in conformity (solenoïd valves, electrode effectiveness). In the event of a fault, the controller issues an alarm signal to warn the user of the maintenance to operate.
Operation: BAMOSOFT comprises two solenoid valves that successively pass raw water then softened water on a specific ion electrode Ca⁺⁺ / Mg⁺⁺ . The specific hardware carries out the analysis of ionic activities, compares data and proceeds to diagnostic routines. The device then delivers the following information: correct measurement, alarm, defective valve, brine leakage, etc. Samples are wasted to drain after each analysis.
When the first cycles of measurement are stable, BAMOSOFT operates a control each 15 min.
The measuring cycle may be started by an external signal (pulse from a counter or an external contact).