ITU404 – ITU414 Panel Mounting Indicators
- Lead Time: 4~6 weeks

- Versatile display indicator, programmable
- Inputs: mA, V, Pt 100, Ni 100, TC, Potentiometric input
- Power supply: 21.6 to 253 V AC 50/60 Hz and 19.2 to 300 V DC
- 4 digits Display / LED 14 segments
- Power supply to sensor: 15 to 25 V DC ; 0/4-20 mA
- Housing 48 x 96 mm
- Protection: Front IP 65
- Models:
- ITU404 includes 4 relays, SPDT
- ITU414 includes 4 SPDT relays plus 1 analogue output 0/4-20 mA
Power supply: | 21.6 to 253 V AC 50/60 Hz and 19.2 to 300 V DC |
Power consumption: | 3.8 W |
Inputs: |
Current: -1 to 25 mA, Voltage: -20 mV to 12 V DC RTD (Pt 100. Ni 100) and resistor TC (Types B, E, J, K, L, N, R, S, T, U, W3, W5 & LR) |
Operating temperature: | -20 to +60 °C |
Outputs: | 4 Relays SPDT, 230 V AC Analogue: 0/4-20 mA, 800 Ω max. |
Power to sensor: | 15 to 25 V DC / 0 to 20 mA |
Case: | DIN 43700, IP65, black polycarbonate, 230 g |
Mass: | 230 g |
Electric connections: | Fast coupling connectors (no screws) |
BAMO ITU402 – ITU412 panel mounting indicators are designed for local process controls as well as specific linearization on non linear input signal (e.g. no volume in tank, not proportional to liquid height). Both models are versatile and programmable displays that are convenient for local control of processes where ambient conditions are severe and humid.
The 4 digits display LED of 13.8 mm high / 14 segments, has a resolution from 1999 to 9999 with a floating decimal point; it shows as well the relay status (ON/OFF) of each relay. All parameters are set up through the front keyboard. A multi-language help file is available through the menu. Supplementary functions for specific linearization and special input signal, are available with programming routine through a PC using software “Preset”. During startup, a test for simulation may be run on each relay without a real input signal. Both indicators provide a simple programming routine. These IP65 indicators are of a DIN 43700 cutout: 48 x 96 mm, to fit in industrial cabinets.