- Approval [EEx ia] IIC ATEX II (1) G/D
- Main power 230 V AC
- Input and output: 4-20 mA
- DIN rail mounting
| Measuring loop: | 1 |
| Main power: | 230 V AC ±10 % / 48 to 62 Hz (indicator of powered unit) by a green LED on front board) |
| Consumption: | ≤ 2.7 W |
| Mounting: | In safe area Input: s.i. – Output not s.i. |
| Loop powered for transmitter, 2 wires, active or passive: |
≥ 15 V DC with current of 21 mA |
| Input signal from hazardous area: |
0/4-20 mA |
| Output signal in and to safe area: |
0/4-20 mA |
| Input impedance: |
Current: 50 Ω ±2 % Voltage |
| Load resistance: | Current: ≤ 800 W Voltage: ≥ 10 kW |
| Accuracy: | ≤ 0.2 % of F. S. |
| Linearity: | ≤ ±0.1 % |
| Voltage powering: | ≤ ±0.01 % / % Ualim |
| Output resistance: | ≤ ±0.01 % / 100 Ω |
| Temperature influence: | ≤ 150 ppm / °C |
| Response time: | ≤ 350 ms |
| Galvanic insulation between Input / Output / Supply: |
2500 V AC / 50 Hz |
| Installation: | In safe area |
| Case: | In ABS |
| Mass: | 200 g |
| Storage temperature: | -25 to +70 °C |
| Operating temperature: | -20 to +60 °C |
| % R. H.: | 5 to 95 % (without condensing) |
| Connectors: | Plug-in, clamp terminals |
| Fitting: | Rail acc. EN 50022 |
BAMO BXNT intrinsic safety converter (input s.i., output non s.i.) with galvanic insulation allows powering of measuring loop or conversion of analogue signal from a transmitter (passive or active) installed in an hazardous area.