Skip to content

Bamotop Frequency Converter

Brand: BAMO
BAMO Mesures Bamotop Frequency Converter, ISME Malaysia
  • 1 Frequency input
  • Power supply to sensor
  • 2 Analogue outputs (current or voltage)
  • 2 Relay outputs
  • Set up through a joystick or a PC
  • Universal main power input: 80 to 256 V AC 50/60 Hz ; 20 to 240 V DC
  • Total insulation: Inputs, Outputs, Power / 2500 V AC
Main power supply:  0 to 256 V AC 50/60 Hz and 20 to 240 V DC (no polarity)
Consumption:  < 4 VA
Display:  Graphic LCD screen
Temperature limits:  Ambient: -10 to +60 °C
Storage: -25 to +80 °C
Protection:  IP 20
Mounting:  DIN rail, 17.5 mm
Connections:  4 removable terminal blocks
Set up:  Through its joystick or with a PC
Accuracy:  0.1 %
Conversion:  Digital / Analog output: 16 bits
Thermal drift:  < 25 ppm
Frequency:  1 Hz to 1 kHz
1 Hz to 1 kHz
100 Hz to 100 kHz
Voltage:  Sine, square, triangular, trapezoidal
From 1 V to 500 V
Input impedance: 3 MΩ

PNP/NPN or potential free contact
Power to sensor: 15 V / 25 mA

Insulation:  Power / Input: 2500 V AC, 50 Hz, 1 min
Input / Analogue output: 2500 V AC, 50 Hz, 1 min
Analogue outputs 1 / 2: No insulation
Power / Analogue output: 2500 V AC, 50 Hz, 1 min
Current:  0-20 / 4-20 mA (Impedance < 700 Ω)
Scalable range: 0 to 22 mA
Residual ripple: < 20 μA
Voltage:  0-10 V (Impedance > 2 kΩ)
Scalable range: 0 to 11 V
Residual ripple < 10 mV
Relays:  SPDT – 500 mA / 250 V

Bamotop is designed to convert a frequency signal into an analogue signal (ie. Inputs signals from dry contacts, CMOS and TTL circuits, magnetic sensors, PNP/NPN sensors). Bamotop receives a frequency input signal that it processes numerically to convert it into an analogue voltage or current signal. Two analogue outputs can be assigned in mA or mV; Two relay outputs can be set over the entire input scale (value, hysteresis and time delay).