- Treatments of fresh water and sea-water
- Surfactants: partial tolerance
- Low incidence of pH changes
- Temperature: 45 °C max.
- Pressure: 3 bar max.
| Measured parameter: | Free chlorine |
| Chlorination additives: | Inorganic compounds, such as NaOCl – Ca(OCl)₂ – – gaseous chlorine, chlorine by electrolysis
Surfactants: partial tolerance |
| Measuring system: | Closed cell with 3 electrodes and electrolyte |
| Supply voltage: | 12 … 30 V DC (Load 500 to 900 Ω) |
| Output signal: | 4 … 20 mA, screw connectors (2 x 1mm²) No galvanic insulation |
| Operating temperature: | 1 to 45°C Automatic temperature compensation |
| Operating pressure: | 3 bar max. (No vibrations, no pulsating flow) |
| Flow rate: | About 30 l/h |
| pH operating range: | 4 to 9 pH – low incidence of pH changes |
| Conductivity: | For sea water up to 50 mS/cm |
| Interferences: | Incidence of ClO₂ and O₃ on measuring signal High level of combined chlorine may have an incidence on measuring signal |
| Zero adjustment: | Not necessary (from factory) |
| Slope calibration: | Only 1 point with BAMOPHAR 194 according to directive DPD-1 |
| Materials: | PVC-U and AISI 316 Ti |
| Dimensions: | O.D. 25 mm, length 220 mm (4-20 mA) |
BAMO CS4 free chlorine sensor is suitable for water treatment (for water equivalent to drinkable quality) and sea water.