Skip to content

SMB Sprinkler Measuring Orifice Flow Meter

BAMO Mesures SMB Sprinkler Measuring Orifice Flow Meter, ISME Malaysia
  • Agreement VdS: G 4990049 (Germany)
  • From ND 80 to ND 250
  • Free mounting position & flow direction
  • Indicator: direct mounting or remoted
  • Scales: m³/min or % according directives
Measuring Principle:  Measurement of differential pressure from an orifice plate
Accuracy:  2.5 % F. S.
Operating Pressure:   Max. 16 bar
Installation:  According VdS guideline CEA 4001 chapter 7.4
Process Fitting:  Wafer mount, between flanges DIN EN 1092-1, PN 16
Materials:  Orifice plate: Aluminum, hard coated
Screwed connections: Nickel-plated brass, 1.4308
Ball valves: Nickel-plated brass
Dial gauge: Aluminum, coated

The BAMO SMB sprinkler measuring orifice flowmeter is is used for monitoring efficiency of pump in test piping of stationary sprinkler systems. It works according to the principle of differential pressure created with an orifice plate.

It is integrated into the pipeline between flanges as a wafer flow-meter. A differential pressure occurs at the orifice, which is proportional to square of the volume flow through the pipeline.

The differential pressure is indicated by a differential-pressure gauge. We calibrate on bench the gauge according the flow rates. The instant value of flow rate is directly read on the dial.

The version SMB-OE displays the differential pressure as a percentage value. The operator can read the equivalent flow in m³/min on a label fixed to the casing.

Thanks to its particular articulate design, integration of the SMB is possible in any flow direction. The display pivots by 180 degrees in both directions.

In case of vibrations in the sprinkler system, the SMB may be fitted with flexible capillaries, to remote the gauge.

SMB series:

  • SMB: Reading scale in m³/min
  • SMB-OE: Reading scale in %
  • SMB-..-Minimess: Remote display gauge with flexible capillaries