- Monitoring of oil-water separators
- Autonomous complete system
- Field installation
- Alarm signal: or flashing light or GSM
- Battery protection against discharge and overload
- Applications: Autonomous alarm unit for monitoring oil-water separators according to EN 858.
Models: | BBS-STD includes: – A wall mount cabinet, 300 x 380 x 130 mm – A yoke U-Bolt Kit for pole mounting – An alarm unit NivOil – A battery, 7 Ah – A controller module to protect the battery against excessive discharge or overload. – A solar panel, 5 Wc, on adjustable holderBBS-GYR includes: – A complete system BBS-STD – A flashing light device on the front of the cabinet BBS-GSM includes: |
Cabinet: | |
Operating temperature: | -25 to +60 °C |
Dimensions: | 300 x 380 x 130 mm |
Protection: | IP 56 |
Mass: | 5.8 kg |
Solar panel: | |
Power: | 5 Wc |
Technology: | Polycrystalline multi panel |
Dimensions: | 365 x 195 mm |
Mass: | 1.8 kg |
Battery: | |
Power: | 7 Ah |
Dimensions: | 150 x 100 x 65 mm |
Flashing light device | |
Dimensions: | Ø 75 x 45 mm |
GSM module: | |
Dimensions: | 75 x 45 x 25 mm |
BAMO Bamobox Solar (BBS) system includes alarm unit NivOil CU/12 and a solar panel to charge a battery, protected against excessive discharge or overload. NivOil is powered hourly, for 3 minutes, to check for a fault and alarm condition. In case of occurring an alarm, the signal is emitted or through a flashing light or through a GSM module.
The working time without sunlight is about 12 days at any period of the year for reliable monitoring even without sun shining days (referring to Greenwich latitude).
Option:
- Flashing light: With the option flashing light, an alarm corresponds to an intermittent light emission (of a Xenon bulb) on the outside of the cabinet. This option is recommended to avoid connecting the NivOIL contact outputs far away minimizing the cost of installation.
- GSM: With the option GSM, the alarm is transmitted long-distance through an SMS message: idoneous when the system is installed in a remote location. The message SMS sent, indicates the BBS identification, the alarming channel (probe), and a pre-recorded message.
Installation:
The cabinet may be mounted on a wall or on a poll (Yoke U-Bolt Kit provided). The solar panel, with its own fixing system, is adjustable regardless of the position of the cabinet.
The BBS must always be mounted outside the hazardous area. Only NivOiL probes can be installed in the hazardous area.