Bamoleak Leak Localizer and Detector

Brand: BAMO
BAMO Mesures Bamoleak Leak Localizer and Detector, ISME Malaysia
  • Leak localization
  • Length up to 3,000 metres (12 areas)
  • Automatic recognition of loop parameters
  • Event recording (date / time)
  • Outputs: 4-20 mA, MODBUS RTU, relays
  • Applications:
    • Building automation
    • Datacenters
    • Semiconductor Industry
    • Clean rooms
    • Archives storage / Libraries / Museums
    • Heating and air conditioning systems
    • Switching centers, computers room
Power supply:  100 to 240 V AC – 50/60Hz or
10 to 30 V DC; 12 to 24 V AC
Consumption:  2 to 5W
Contact outputs:  5 contacts, adjustable, potential-free
To set as, or N.O. or N.C. contact

Note: All contacts are open when de-energized

Switching power:  250 V AC, 2 A / 30 V DC, 1 A

Caution: Contacts are not protected against overload, provide an external protective device

Maximum cable length:  3,000 m
Housing:  46 x 100 x 127 mm
Rail mounting (DIN EN 50 022; 35×7.5 mm)
Protection:  IP40

Note: The protection against accidental contact according to DIN EN 61010-1 is only guaranteed when the unit is installed in a closed cabinet with a protection IP5x or greater.

Ambient temperature limits: -10 to +45 °C
Sensor (cable) temperature limits:  -50 to +150 °C
Connectors temperature limits:  -20 to +60 °C
Wall-mount cabinet (option):  175 x 200 x 155 mm
Screw terminals:  Screw connectors, cable diam. Max. 1.5 mm²
Detection areas:  12 areas; Setting of name/ TAG to each one
Accuracy of leak localization:  < 1 %; ±1 m
Measuring loop:  1 input for the 4 poles sensor (cable)
2 additional inputs for 2 one-point detectors (e.g. MAXITOP LWC or LWC B)
Power supply to the detection loops:  Localization with sensor (cable): Max. 20 V AC/DC; Max. 5 mA
One-point detectors: Max. 30 mA (each)
Analogue output 4-20 mA Active signal output (with its own loop power)
4 to 5 mA: No alarm
5 to 20 mA: Localization of the detected leak point = [ cable length x (current value – 5mA) ] / 15mA
Adjustable timer:  When detection occurs: 0.5 to 5 minutes delay before signaling
Real-time clock:  Integrated clock with battery, automatic summer time switch can be activated
Records:  Automatic record of all events, max. 48 inputs, events can be acknowledged and deleted, individually
Language:  To choose between English, German, French, Spanish, Portuguese, Polish
Key protection of settings:  4 digits; Can be deactivated
Signaling interface:  Display:
2 line-text LCD
Status of contact outputs
5 LED (multicolour)
Digital communication:  RS485 / MODBUS
Selecter: Rotary switch on front panel

Bamoleak allows securing work areas where leaks are prejudicial for equipment, by detecting and precisely locating leaks of conductive liquids. The sensor (cable) is laid along the monitored area or pipeline, and, connected to the evaluation unit. Leakage is detected by the converter, which determines, records and reports information via the analog output, relays and the RS485 Modbus interface.

Two complementary detectors can be connected to the converter such as Maxitop LW C (detection in double-walled tank) or LWC-B (local floor detector).

Note: BAMOLEAK can locate one leak at a time.