Skip to content

BXNT Intrinsic Safety Converter

Brand: BAMO
BAMO Mesures BXNT Intrinsic Safety Converter, ISME Malaysia
  • Approval [EEx ia] IIC ATEX II (1) G/D
  • Main power 230 V AC
  • Input and output: 4-20 mA
  • DIN rail mounting
Measuring loop:  1
Main power:  230 V AC ±10 % / 48 to 62 Hz
(indicator of powered unit) by a green LED on front board)
Consumption:  ≤ 2.7 W
Mounting:  In safe area
Input: s.i. – Output not s.i.
Loop powered for transmitter,
2 wires, active or passive

≥ 15 V DC with current of 21 mA
Input signal from hazardous area
0/4-20 mA
Output signal in and to safe area
0/4-20 mA
Input impedance:
Current: 50 Ω ±2 %
Voltage
Load resistance:  Current: ≤ 800 W
Voltage: ≥ 10 kW
Accuracy: ≤ 0.2 % of F. S.
Linearity:  ≤ ±0.1 %
Voltage powering:  ≤ ±0.01 % / % Ualim
Output resistance:  ≤ ±0.01 % / 100 Ω
Temperature influence:  ≤ 150 ppm / °C
Response time:  ≤ 350 ms
Galvanic insulation between
Input / Output / Supply

2500 V AC / 50 Hz
Installation:  In safe area
Case:  In ABS
Mass:  200 g
Storage temperature:  -25 to +70 °C
Operating temperature:  -20 to +60 °C
% R. H.:  5 to 95 % (without condensing)
Connectors:  Plug-in, clamp terminals
Fitting:  Rail acc. EN 50022

BAMO BXNT intrinsic safety converter (input s.i., output non s.i.) with galvanic insulation allows powering of measuring loop or conversion of analogue signal from a transmitter (passive or active) installed in an hazardous area.