Skip to content

Capsytron TLS Dry Run Protection

Brand: BAMO
BAMO Mesures Capsytron TLS Dry Run Protection, ISME Malaysia
  • Wet parts in plastic materials
  • Compact probe
  • Plug for function test
  • Switches when pipe is empty
  • No moving parts
  • Applications:
    • Protection against dry run; Detection of empty filling pipe
    • Prevents hammer effects when air is compressed in the pipe
Power supply:  15 to 27 V DC
Consumption:  < 1 W
Output:  Potential free Reed contact
N.C. with liquid; N.O. without liquid (in air)
Rated: Max. 50 V AC / DC; Max. 0.5 A; Max. 10 VA for PLC connection or coupling relay
Connector:  Screw terminals, IP 20, cable Max. 2.5 mm²
Additional function:  Connection to an external test button, with which the whole electronics, wiring and signaling device can be tested.
Probe:  PE, or PP
Length:  Min. 95 mm
Fitting:  Union nut BSP 1”, includes EPDM o-ring
Ambient temperature:  -20 to +60 °C
Pressure limit:  2 bar
Housing terminal:   PBT, IP 65 acc. EN 60529

Caution:
When supply is switched on, the output contact remains closed about 0.5 second during the auto-test routine.

The Capsytron TLS sensor is of one piece; Previous series had 1 detector and 1 reference electrode, separated of each other (SFL / SFL BZ). To adapt actual model to an old series holder, we recommend to plug i

BAMO Capsytron TLS is designed for empty tube detection. It avoids hammer effects when filling a tank. It is designed to detect the presence of liquids whose reactance is 50 pF. In no case should liquids form insulating or conductive deposits.