- 1 Reed contact N.O. / N.C.
- Stainless steel or brass versions
- Low pressure drop
- Fittings: On tee up to DN50 or BSP ½”
- Applications: Detection of presence or absence of flow of a liquid in a pipe under pressure. The liquid must be free of magnetic particles.
Body: | AISI 316 Ti Brass |
Seal: | FPM on stainless steel version NBR on brass version |
Temperature limit: | 110 °C (other on request) |
Ambient temperature: | 70 °C |
Pressure limit: | 25 bar |
Fittings: | DN 10 to DN 50: Tee with BSP female threads ND 50 and larger: male thread BSP ½” |
Contact output: | N.O. or N.C. according to the Reed contact orientation |
Switching power: | 230 V / 1.5 A / 80 W / 90 VA max. |
Output cable: | PVC; 3-wire; 1 mm² ; 1.5 m long |
Trigger point adjustment: | ±15 % of table values, horizontal pipe (Refer to datasheet) |
Protection: | IP 65 |
Caution: Thresholds are for water at 20 °C and for a flow in horizontal pipe. Mounting could be on a vertical pipe with ascending flow; Then, threshold value will be greater than the one from the table. The pipe slope of a flowing down piping must be less than 40 %.
The BAMO CDP operates a switch outside the liquid: The flow drives the paddle. A magnet on top of paddle actuates a Reed contact, located outside the fluid. The reverse movement of the paddle is generated by a leaf-spring. These controllers offer a simple, reliable and inexpensive solution for flow monitoring in pipelines.
These controllers offer a simple, reliable and inexpensive solution for flow monitoring in pipelines.
CDP controllers are mounted in-line, pipes up to ND 50 with a Tee, BSPF threads. For larger diameters, CDP must be mounted on-line, on an adaptor BSP ½” female thread.
Note: The Reed contact has a low switching power: The use of a relay ES 2001 will protect the Reed and allows a remote loop signal with greater breaking capacity on a change-over relay output (500 VA/ 250 V A / 5A – 1A/ 125 V DC/ 40 W).