- For all electrical conductive liquids
- Suitable for level or leakage detection
- Adjustable sensitivity and timer, selection of action mode
- Self diagnostic with instant alarm (LED) for: Short circuit on the loop detection, loop detection cable break off
- Functions: On/ Off level controller between 2 rods, level regulation between 3 rods, leakage, inundation and humidity detection
Power supply input: | 230, 115, 48, 24V AC – 50/60Hz 12, 24V DC |
Consumption: | < 2VA |
Ambient temperature: | -15 to +45°C |
Mass: | 100g |
Mounting: | DIN rail (DIN 46277) |
Dimensions: | 22.5 x 75 x 99mm |
Protection: | IP40 – Tropicalized on request (varnish) |
Hysteresis: | About 10% of sensitivity |
Adjustable timer: | 0.5 … 3 s (increase and decreasing signal) |
Sensitivity: | Low range = 1 to 70 kΩ High range = 15 to 150 kOhm |
Current loop output: | Galvanic insulated, < 6V ac / < 2mA |
Relay outputs (2): | Max 250 V, 3 A [AC] Max 125 V, 0.3 A [DC] |
CE Labels: | In accordance with low voltage guidelines (2006/95/EEC) and (89/336/CEE) |
Models: | ES5000 /230: Relay, input power supply 230 V / 50-60 Hz ES5000 /115: Relay, input power supply 115 V / 50-60 Hz ES5000 /48: Relay, input power supply 48 V / 50-60 Hz ES5000 /24: Relay, input power supply 24 V / 50-60 Hz ES5000 /12 V DC: Relay, input power supply 12 V DC ES5000 /24 V DC: Relay, input power supply 24 V DC |
Relay for level control
Minimal or maximal levels – Dosing, flow detection and alarm, pump control, solenoid valve control, fluid detection in a pipe.
Relay for leakage, inundation and humidity detection
In use with a BAMO L.I.S.A. sensor, the relay ES5000 is dedicated for leakage detection on water distribution (pipes, sprinklers) and alarming in case of water, condensates or humidity in areas where water is prejudicial for equipments. The relay ES5000 includes a self diagnostic of the detection loop (short circuit on the loop detection and ribbon sensor break off) in order to warranty a positive safe detection system.