- Float level fail-safe detection
- For aggressive and non electrically conductive liquids
- Positive active alarm
- Auto diagnostic system and LED indication when in use with a SHR C transducer
- Approvals: DIBT Z-65.40-272, for leakage detection, WHG §19 when in use with a SHR C transducer
Main power supply: | 24 V DC ±10%; caution: DC current circuit should be protected by a fuse of 250 mA |
Power consumption: | Approx. 3W |
Operating pressure: | Atmospheric, 0.8 to 1.1 bar |
Ambient temperature: | -20 to +60°C |
Material: | PE-HD |
Cable: | TPK, 2 x 0.5 mm2, shielded |
Hysteresis: | About 2 mm |
Terminal housing: | PBT, fibre glass reinforced, IP 65 acc. EN 60 529 |
Terminals: | Screw connectors, IP 20; max. wire cross-section 2.5 mm2 |
Output: | To a transducer MAXIMAT SHR C. Cable length 300 m maximum, wire cross section 0.5mm2 as a minimum |
BAMO Maximat LW VK is ideal for permanently survey risks of leakage of a liquid from storage tanks, filling equipment, dosing pumps etc. Convenient to use with non-electrically conductive liquids, oils, emulsified, non-flammable, water endangering liquids. It is a perfect instrument to detect fluid in a double-wall tank. Maximat LW VK operates with liquids of specific weight from 0.7 g/cm3.
The sensor Maximat LW VK is designed to detect conductive liquids non-electrically conductive. The detection results from the position of a magnet inside the float and a Reed contact inside the probe. It is necessary to use it with a SHR C transducer. The liquids may not generate deposits originating jamming of float.