- 1 surveying channel, wall mounting
- For compact overfill and leakage sensors MAXIMAT and MAXITOP
- Automatic loop detection survey
- Automatic sensor test
- Alarms: Optical and acoustic (>75 dB)
Supply power: | 230V AC ±10% – 50/60Hz |
Power consumption: | Approx. 2VA / 2W max. |
Protection: | IP65 (acc. EN 60 529) |
Ambient temperature: | -20 to +60°C |
Electric connections: | Polycarbonate, Wall mounting |
Input: | 1 detector |
Electric connections: | Screw connectors |
Output: | 1 changeover contact |
Switching power: | 230V AC / 3A |
Indications: | Green LED ––> in operation Yellow LED ––> alarm not yet reset Red LED ––> alarm in curse |
Audible alarm: | >75 dB |
Control elements: | Reset push button for test and alarm acknowledgement |
CE Mark: | In accordance with low voltage directive (2006/95/EC) and EMC directives (2004/108/EC) |
BAMO Maximat TC1 is designed for overfill detectors and leakage detectors Maximat and Maxitop. Alarm system TC1 has a self-diagnostic test; it surveys the sensor, the loop and completes all the alarm procedure.
Acoustic alarm complies with directives (ZG-ÜS) for overfill detectors. The detector is directly powered through the TC1. Alarm status is provided by detector to TC1 witch signals it with audible and visual alarms. The alarm reset is done by operator on the front board.
On request: TC1B version allows to connect any sensor, which have a potential free contact output.