- 4 surveying channels, wall mounting
- For compact overfill or leakage sensors
Maximat C, Maximat VK, Maximat LW - Microprocessor controlled
- Automatic sensor detection and survey
- Sensors and loops tests integrated
- Optical and acoustic (>75 dB) alarms
Supply power: | 230 V AC ±10% 50/60 Hz, or 24 V DC ±10% |
Power consumption: | Approx. 6 VA / 6 W max. |
Ambient temperature: | -20 to +60°C |
Housing protection: | IP 65 (acc. EN 60 529) 200 x 205 x depth= 100 mm |
Sensor supply power: | 15 V DC, short circuit proofInput: max. 4 sensors 1 external reset contact |
Outputs: | 4 floating changeover contacts (1 contact per sensor) 1 floating changeover contact for group alarm 1 floating changeover contact for external horn |
Contact rating: | 250V AC / 115V DC – 500VA / 3A |
Indication: | Red blinking = not acknowledged alarm Red steady burning = acknowledged alarm Yellow blinking = sensor malfunction Yellow steady burning = test is running Green steady burning = sensor in operation Green LED Off = no sensor connected1x piezo – signalization horn >75 dB (A)/1m1x extra bright flash LED for sum. alarm |
Control elements: | Reset push button for alarm acknowledgementPush button for system test |
CE Mark: | In accordance with low voltage directive (73/23/CEE) and EMC directives (89/336/CEE) |
The BAMO TC4 device has built in self test, survey of the connected sensors and the complete alarm processing – accordingly to approval guidelines for overfill sensors (ZG-ÜS).
Note: The function test with the external push button does not replace the annual operation test, which is specified in the German specifications DIBt-ZG-ÜS § 6.2.