Skip to content

Maxitop LWC B Floor Leakage Detector

Brand: BAMO
BAMO Mesures Maxitop LWC B Floor Leakage Detector, ISME Malaysia
  • Capacitance detection loop
  • For aggressive and conductive liquids
  • Fail-safe; Self-diagnostic of loop integrity with SHR or TC4 or TC1
  • Wet parts in plastic materials
Power supply:  15 to 26 V DC
Consumption:  About 1 W
Ambient temperature:  -20 to +60 °C
Housing:  PBT; IP 67 (EN 60529)
Cable output:  Standard length: 6 m
5 x 0.5 mm², shielded, PVC sheath
Trigger point:  Minimum height of liquid:1 mm

BAMO Maxitop LWC-B is ideal to give an alarm when leakage occurs on the floor of retentions or collecting areas. With its fail-safe detection loop, it is permanently operational. It is designed to detect conductive liquids with a reactance of up to 5 kOhm/cm and when the coupling capacitance towards the ground is more than 50 pF. The liquids may not generate electrical insulating or conductive deposit.

BAMO Maxitop LWC-B has 5 different types of connections:

  • Contact output, low voltage (Max. 50 V AC/DC; Max. 0.5 A; Max. 10 VA)
  • Relay output, adding a relay converter CST
  • Output relay, adding a relay converter SHR
  • Direct connections to a PLC
  • Signaling events on-site, with devices TC4 or TC1