- Construction: all in plastic materials
- PVC or Polysulfon
- Direct reading
- 2 set point indicators
- Alarm contacts in option
- Accuracy: Class 4
- Radial mounting: vertical, ascending flow
Max pressure at 20°C: | 10 bar |
Temperature limits: | 1) PVC: 0 to 50°C (water) 2) Polysulfon: 0 to 90°C (max 60°C with PVC fittings) |
Float material: | PVDF |
Float stopper: | PVDF |
Float guiding rod: | DN50 & DN65 only, stainless steel with PVDF coating |
Seals material: | EPDM (FPM on request) |
Unions connection (standard model): | PVC, for solvent welding on site |
Scales: | Standard in L/h of water at 20°C |
MEASURING RANGE
PDP Type | DN | D (mm) | R | Flow Range (L/h) | ΔP (mbar) |
2.5 | 10 | 16 | 3/8″ | 2.5 – 25 | 4.5 |
5 | 10 | 16 | 3/8″ | 5 – 50 | 4.5 |
10 | 10 | 16 | 3/8″ | 10 – 100 | 4.5 |
15 | 15 | 20 | 1/2″ | 15 – 150 | 4.4 |
20 | 15 | 20 | 1/2″ | 20 – 200 | 4.4 |
30 | 25 | 32 | 1″ | 30 – 300 | 8.1 |
50 | 25 | 32 | 1″ | 50 – 500 | 8.1 |
100 | 25 | 32 | 1″ | 100 – 1000 | 8.1 |
PDP series flow-rate indicators are ideally suited for continuous monitoring of flow for water, with body material in PVC or PSU. The fluid flow raises a diver in a conical tube, expanding the cross section of the passage of fluid. The diver moves up proportionnaly to the flow-rate. The PDP rotameter must be installed vertically with rising fluid. It is recommended to have a length upstream of 10x DN and a length downstream of 5x DN.