- Floor stand detector, compact unit
- Without moving parts
- Built-in relay
- Cable output, 5m long PVC cable
Main power supply: | Input for 24 V DC (18-30 V DC) Maximum of 20 mA |
Sensitivity: | Detection within 0.8 to 1MΩ |
Detection current: | Around 1 mA ac |
Relay: | Contact 60 V / 0.5 A max. |
Dimensions in mm: | Length 50 x Width 35 x Height 25 |
Cable: | PVC, length of 5 m (5 wires x 0,14 mm2) |
Operating temperature: | -20°C to +60°C |
Mass: | 100 g (without cable) |
EC marks: | according (2006/95/EEC) and (89/336/CEE) |
The device is use to control if electrically conductive fluids are on site or are not. Single point detection of leakage in basin, drain, etc.
Two electrodes are permanently separated and electrically insulated from each other. The detector monitors the open circuit. When an electrical conductive fluid joins the two electrodes, the resistive detector actuates a relay.